3.Technical specifications
| Item | Specification |
|---|---|
| Product Model | M1L385-40 II (2P) |
| Rated Voltage Un | 230VAC |
| Maximum Continuous Operating Voltage – Uc | L-N:385VAC; PE-N:255VAC |
| Nominal Discharge Current – In (8/20μs) | 20kA |
| Maximum Discharge Current – Imax (8/20μs) | 40kA |
| Voltage Protection Level – Up (In) | 1.8kV |
| Transient Overvoltage Characteristic UTOV | 400V/5sec |
| Withstand Short-Circuit Current | 25kArms |
| Front-Fuse | 125AgL |
| Terminal Wiring Range | 1.5 mm² ~25mm² (Flexible)/35mm² (Rigid) |
| Alarm Port Maximum Operating Current | 250V/0.5A (AC) 0.1A (DC); 125V/1A (AC) 0.5A (DC) |
| Enclosure Flame Retardant Rating | UL94 V-0 |
| Enclosure Protection Rating | IP20 |
4. Principle of Protection